What a Manual J report contains, 2026 prices from $45 to $990, the code rules, and a 15-point checklist for checking a contractor's load calculation.

By Air Conditioner Guide Editorial TeamPublished July 10, 2026Updated November 10, 2026Reviewed by Air Conditioner Guide Editorial Team
Detailed architectural blueprint showing elevations and building dimensions
A load calculation turns the actual house and design conditions into required capacity.Photo on Unsplash

The short answer

Manual J (ANSI/ACCA 2 Manual J-2016, 8th Edition) calculates each room's heat loss and its sensible, latent and total heat gain at local design conditions; Manual S then picks the equipment. Published prices checked November 10, 2026 run from $45 per project in ACCA-approved software and $100 to $179 for a remote report to $350 to $795 at engineering or on-site firms, with Manual J, S and D packages listed from $199 to $990 and up. A sound report uses 75°F indoors for cooling and 70°F for heating, ACCA Table 1A outdoor temperatures, bedrooms plus one occupants at 230 Btu/h sensible and 200 latent each, and no safety factor.

A Manual J load calculation is ACCA's ANSI-recognized method, ANSI/ACCA 2 Manual J-2016 (8th Edition), for working out how much heat each room gains on a design summer day and loses on a design winter night, in sensible, latent and total Btu per hour. Published prices checked November 10, 2026 run from $45 per project in ACCA-approved software you run yourself, through $100 to $179 for a remote report, to $795 for an on-site scan, delivered within hours to 7 business days. Manual J does not choose the air conditioner; Manual S does. A report is only as good as its inputs, so this guide shows what a real one contains and which numbers to check.

Quick answer

QuestionShort answerBasis
What is it?ACCA's residential load standard, 8th Edition, Version 2.50ANSI recognition, August 2016
What does it output?Heat loss plus sensible, latent and total heat gain per room and for the houseACCA
What does it cost?$45 DIY; $100 to $179 remote; $350 to $795 at engineering or on-site firms8 price pages, Nov 10, 2026
J, S and D together?From $199 remote; $520 at a HERS-rater firm; from $990 at an engineering firmSame
How long?Same day to 7 business days after plans arriveSame
Required?Where IRC M1401.3 or IECC R403.7 is adopted; enforcement is local2021 IRC, state codes
What it does not doChoose equipment (Manual S) or size ducts (Manual D)ACCA

How we built this guide

  • The standard: ACCA's Manual J page, its August 9, 2016 release on ANSI recognition, and its November 5, 2025 notice proposing to reaffirm the 2016 edition unchanged.
  • Real reports: three reports from ACCA-approved software posted publicly on Green Building Advisor's Q&A forum: an Elite RHVAC report for a 1,537 sq ft Baltimore house (October 2023), and two 2019 Wrightsoft reports, for a 3,203 sq ft Maryland house by Energy Vanguard and a 1,932 sq ft Arlington, Massachusetts house by Bruce Harley Energy Consulting.
  • Review checklists: the International Code Council's 2017 CodeNotes on verifying Manual J, ENERGY STAR's National HVAC Design Report Rev. 14 (January 2025), a September 2018 Texas Department of Housing and Community Affairs guide, and December 2022 NYS Clean Heat infiltration guidance.
  • Prices and code: eight providers' published price pages, checked November 10, 2026, and the 2021 IRC as adopted in Seattle, Virginia's 2021 code, Washington's energy code and Pima County, Arizona's permit rules, checked October 16, 2026.

We did not commission a Manual J, measure a house or test software.

Manual J, Manual S, and Manual D

StepQuestion it answersWhat you should receive
Manual JHow much heating and cooling does each room need?Block and room-by-room load summary plus assumptions
Manual SWhich actual equipment performs correctly at those conditions?Selection using OEM expanded performance data
Manual DCan the ducts deliver the required airflow quietly?Supply and return sizing, airflow, pressure, and register plan

A "3-ton" unit does not deliver the same capacity under every condition, so Manual S checks real performance against the loads. Watch for shortcut lines: Wrightsoft can print "Req. total capacity at 0.70 SHR", and the Elite report we read printed "Recommended 3.05 tons" from an assumed 75 percent sensible capacity. Energy Vanguard's Allison Bailes calls such lines a guess until a designer has run the equipment's performance data. A real Manual S page names the condenser, coil and AHRI reference.

What a Manual J report includes, section by section

Wrightsoft prints a "Project Summary" or a shorter "Load Short Form"; Elite prints a "Project Report" with "Check Figures". A complete report covers the same ground either way.

SectionWhat it showsWhat to check
Project informationAddress, date, designer, software and versionSoftware on ACCA's list; dated after any upgrades
Design conditionsWeather station, outdoor dry and wet bulb, indoor temperature and humidity, grains differenceNearby station; 75°F cooling, 70°F heating
ConstructionEach wall, ceiling, floor, door and window with area and U-value; SHGC for glassMatches the house today
InfiltrationMethod, tightness category, air changes per hour and CFMBlower door result if one exists
VentilationOutdoor air CFM from a fan or ERVOnly fans that run continuously
DuctsLocation, insulation, leakage, duct gain and loss in Btu/hZero only if ducts are indoors
Internal gainsOccupants, appliances, lightingBedrooms plus one; 1,200 or 2,400 Btu/h appliances
Room-by-room tableHeating and cooling load and CFM per roomEvery room has an airflow target
Building totalsHeat loss, sensible, latent and total gainLatent shown separately
Exposure diversity (AED)Whether glass load spikes at one hourRequired statement under the 2016 standard
Equipment summaryMake, model, AHRI reference, capacities, airflow, static pressureFilled in, not "n/a", once equipment is quoted

Two lines need explaining. AED, adequate exposure diversity, covers houses with most glass facing one way: the Elite report allows a peak-hour glass load up to 30 percent above the 12-hour average, and because its house peaked 35.3 percent above the average, the software added a 452 Btu/h "AED excursion". Wrightsoft's rate/swing multiplier, 0.93 to 0.96 in the reports we read, scales the sensible load down. Both are part of the method, not padding.

What three public reports show

ItemBaltimore, 2023Maryland, 2019Massachusetts, 2019
SoftwareElite RHVACWrightsoftWrightsoft
Conditioned area1,537 sq ft3,203 sq ft1,932 sq ft
Outdoor design, cool / heat89°F / 17°F91°F / 17°F88°F / 9°F
Indoor design75°F / 70°F75°F / 70°F75°F / 70°F
InfiltrationSemi-loose, 0.40 ACHTight, 0.05 ACHAverage
Duct load0 Btu/h0 Btu/hNot on short form
Total cooling33,344 Btu/h9,933 Btu/h14,546 Btu/h
Heat loss30,006 Btu/h13,146 Btu/h37,892 Btu/h
Sq ft per ton503About 3,870About 1,590
  • Two Maryland reports, two weather stations. One used 89°F, the other 91°F at BWI airport. Energy Vanguard treats a couple of degrees as minor and a 5°F gap as an error to fix.
  • Internal gains can swing a result. The Baltimore report's equipment line was 10,100 Btu/h sensible, about a third of its cooling load, for a house with two kitchens. Manual J's standard appliance allowance is 1,200 or 2,400 Btu/h.
  • A short form is not enough to audit. The Massachusetts summary shows no U-values, infiltration rate or duct line. The Texas guide warns that construction pages may not come with a report unless you ask.

How to check a Manual J: 15 points

The ICC's CodeNotes ranks inputs by effect: design temperatures first, then windows and glass doors, ducts, and ceilings under an attic. Infiltration and ventilation sit in the middle; insulated walls and floors and internal gains matter least.

Design conditions and internal gains

InputWhat it should sayRed flag
Indoor cooling75°F at 50% RH (45% dry climate, 55% humid)72°F or lower
Indoor heating70°FHigher than 70°F
Outdoor coolingACCA Table 1A 1% value, nearest station5°F or more above it
Outdoor heatingTable 1A 99% valueColder than the table
OccupantsBedrooms plus oneMore, without a stated reason
People load230 Btu/h sensible, 200 latent eachHigher per-person values
Appliances1,200 or 2,400 Btu/h, or an itemized listA large unexplained number

Table 1A values for 15 cities, from Phoenix's 108°F to Seattle-Tacoma's 81°F, are in our AC sizing guide; ACCA says to use them as published, with no safety factor. Occupants matter too: Energy Vanguard found 23 people entered for a five-bedroom house, and at 430 Btu/h each the 17 extra people added about 7,300 Btu/h, more than half a ton.

Envelope, air leakage and ducts

InputWhat it should sayRed flag
Window areaTotal and direction match the plansMore than 15 sq ft under or 60 sq ft over
Window U and SHGCValues from the NFRC labelSingle-pane values for low-e glass, or the reverse
Ceiling, wall, floor RWhat is installed todayPlanned upgrades entered as done
InfiltrationBlower door based, or a matching category"Loose" on a house that tested tight
Floor areaWithin 10% of the real conditioned areaGarage or unconditioned rooms counted
Duct locationWhere the ducts actually runAttic ducts modeled as indoors, or the reverse
Duct tightness"Average sealed" or tighterDefault leaky ducts after sealing work
Safety factorNoneA percentage added to the total

The window tolerance is ENERGY STAR's; its design report also wants occupants within 2 of the real count and the predominant SHGC within 0.1. The 10 percent floor-area check is Pima County's rule for replacement permits.

NFRC labels print each window's U-factor and SHGC. The Texas guide puts single-pane glass at a U-value of about 1.22, and the Baltimore report entered clear double-pane vinyl windows at U 0.57 and SHGC 0.56. ENERGY STAR's current criteria show what newer windows carry:

ENERGY STAR zoneU-factorSHGC
Northern0.22 or less0.17 or more
North-Central0.25 or less0.40 or less
South-Central0.28 or less0.23 or less
Southern0.32 or less0.23 or less

In the reports we read, infiltration was picked from a menu. Manual J's Table 5A sets default air changes per hour for five categories, with the range depending on house size:

Manual J categoryCooling ACHHeating ACHBlower door match
Tight0.05 to 0.110.10 to 0.21About 3 ACH50, a code-level house
Semi-tight0.10 to 0.220.19 to 0.41About 3 ACH50
Average0.15 to 0.350.28 to 0.61About 9 ACH50
Semi-loose0.23 to 0.500.43 to 0.95Not mapped
Loose0.30 to 0.670.58 to 1.29Not mapped

The blower door column is NYS Clean Heat's 2022 comparison. If the house has been tested, ask for the measured number, as Energy Vanguard recommends; without a test, Pima County expects replacement jobs to use average, semi-loose or loose.

For ducts, ENERGY STAR says about 20 to 30 percent of the air moving through a typical system is lost to leaks and poor connections. Both full reports we read carried a duct load of 0 Btu/h, which is right only when ducts sit inside conditioned space; attic ducts should show a duct gain. Our ductwork guide covers the measurements.

The bottom-line checks

  • No safety factor. Manual S already lets single-stage equipment carry 90 to 115 percent of the load, so padding the load double-counts.
  • Square feet per ton. Energy Vanguard's 40 recent designs, mostly in the Southeast, averaged 1,431 sq ft per ton, the lowest 624, so a new code-built house near 500 deserves a second look. Existing homes carry higher loads; our screening ranges for them run 430 to 750.
  • The old unit. The Texas guide tells weatherization staff to investigate any result larger than the system being replaced.

Worked example: where the load comes from in an 1,800 sq ft house

This is an illustration built from published Manual J factors, not a Manual J result. The house is one story with 8-foot ceilings, three bedrooms, 270 sq ft of clear double-pane windows (15 percent of the floor), 40 sq ft of doors and 1,130 sq ft of net wall. Design conditions match the Baltimore report: 89°F outdoors, 75°F indoors, a 50-grain moisture difference.

Window, wall and door factors are that report's loads per square foot (its walls are insulated brick). The ceiling row applies its effective 49°F temperature difference (657 Btu/h through 670.6 sq ft of R-50 ceiling at U 0.02) to R-30 and R-19. Air leakage uses the report's 1.1 and 0.68 multipliers with Table 5A air changes, and the attic-duct row uses the 15 percent factor in our sizing calculator because Manual J's duct tables are not public.

ComponentTighter houseLeakier houseFactor used
Windows, 270 sq ft12,80012,80047.4 Btu/h per sq ft
Walls, 1,130 sq ft9009000.82 per sq ft
Doors, 40 sq ft4004009.7 per sq ft
Ceiling, 1,800 sq ft2,900 (R-30)4,600 (R-19)U x 49°F
Air leakage, sensible1,100 (0.30 ACH)1,700 (0.45 ACH)1.1 x CFM x 14°F
Ducts0 (indoors)3,400 (attic)15% of sensible
People, 4920920230 each
Appliances1,2001,200Manual J allowance
Sensible total20,22025,920
Air leakage, latent2,4003,7000.68 x CFM x 50 grains
People, latent800800200 each
Total cooling23,42030,420
Tons1.952.53Total divided by 12,000

All loads are in Btu/h. Windows dominate: 55 percent of the tighter house's load and 42 percent of the leakier one's. The leakier house's ceiling, air leakage and attic ducts add 7,000 Btu/h between them, more than half a ton. Both come out at a sensible heat ratio of about 0.85, inside the 0.8 to 0.9 Energy Vanguard reports for eastern North America. The same arithmetic shows how input choices move the answer:

  • Outdoor design 5°F hotter: about 2,000 Btu/h more sensible load in the tighter house.
  • Indoor design of 72°F instead of 75°F: about 1,200 Btu/h more sensible load, plus more latent load.
  • 10,100 Btu/h of equipment instead of 1,200: 8,900 Btu/h more, about three-quarters of a ton.

Both totals sit below the 3.3 to 4.3 tons our calculator screens for an average 1,800 sq ft house in the hot-humid state group that includes Maryland. A screening range has to cover houses it cannot see; a component load covers one house. Reuse the method, not the number.

What a Manual J costs in 2026

No federal agency publishes Manual J prices; these are the price lists we found, checked November 10, 2026.

OptionPublished priceWhat you getTurnaround
DIY, Cool Calc$45 per projectJ, S and D in approved softwareYour own pace
Remote, EnergyReports.netJ, S and D from $199Priced by size and systemsNot stated
Remote J and S, B&B System Design$100 block, $140 room-by-room under 2,000 sq ftWrightsoft, one system3 to 4 days
Remote J, Manual J Calculator$109 block, $179 room-by-room to 2,900 sq ft$0.10 per extra sq ft48 hours with $100 deposit
HERS raters, REScheckReview$129 J, $89 STo 6,000 sq ftOften within hours
HERS raters, TLC Inspectors$370 J and S; $520 J, S and DTo 2,000 sq ft2 to 7 business days
Engineering firm, LoadCalculationsHVAC$0.14 per sq ft, $350 minimum; J, S and D from $990Wrightsoft, duct layout on plans24 to 48 hours
On-site scan, HVAC Inspections Los Angeles$795 to 2,500 sq ft; $995 to 4,000LiDAR scan, room-by-room reportSet at booking
Contractor bidding the jobVariesAsk for the full reportWith the bid

For an 1,800 sq ft house, a room-by-room Manual J from these lists costs $140 to $795. Remote services model what you send, so their accuracy depends on your plans; an on-site scan measures the house. Against the $6,000 to $9,800 standard-tier band for a 3-ton replacement, $140 to $520 is about 1.4 to 8.7 percent of the job, while going a full ton too big adds $1,500 to $2,700 at standard tier before any circuit or duct changes.

ACCA-approved software and free tools

ACCA keeps the official list and says plainly: "If software is not listed on this page, then it is not ACCA-approved." The Texas weatherization program's 2018 guidance requires approved software on every job it funds.

SoftwareACCA statusPrice foundNotes
Wrightsoft Right-J8Full Manual JNot publishedUsed by two firms above
Elite RHVACFull Manual JNot publishedPrints sq ft per ton
Cool Calc Manual JFull Manual J$45 per project; $50 per user a monthBrowser or LiDAR iPad
Acculoads, EnergyGauge, HVAC ResLoad-J, HeatCAD and LoopCAD MJ8, Conduit Tech, Amply Energy, Zero HomesFull Manual JNot checkedConduit Tech powers the LA scan
Right-J Mobile, CalcuNow MJ8-CalcBlock load onlyNot checkedNo room airflow
ACCA Manual J8 AE SpeedSheetACCA's own Excel sheetFree; needs the manualAbridged cases only
LoadCalc.netNot approvedFree"Not accredited by any organization"

Pima County sums up the SpeedSheet's abridged cases as one zone, glass under 15 percent of floor area, a dark shingle roof and ducts indoors. For a permit or a quote dispute, use an approved program.

Is Manual J required by code?

The 2021 International Residential Code, Section M1401.3, says equipment "shall be sized in accordance with ACCA Manual S" based on loads "calculated in accordance with ACCA Manual J", or other approved methods. Two exceptions let multistage or variable-refrigerant-flow equipment exceed Manual S limits when the loads fall within its published capacity range, and allow the next larger standard size when no unit meets both the total and sensible loads. IECC R403.7 repeats the rule in the energy code, and M1601.1 sends duct design to Manual D.

Code or jurisdictionWhat it saysReplacements
2021 IRC M1401.3Manual S sizing from Manual J loads; two exceptionsWhere the local code applies it
Washington, R403.7No larger than the smallest size that covers the load within oversizing limitsNot stated in the section
Virginia, 2021 codeJ, S and D required since the 2009 edition; a third exception for the maker's smallest unitNot stated
Pima County, ArizonaJ, S and D with the plans; capacity within 6,000 Btu/h of the sensible loadYes, unless in a utility program
ENERGY STAR new homesUnabridged Manual J 8 and the Rev. 14 design reportNew homes only

Pima County is the clearest enforcement example we found: plans without the calculations "will not be accepted for review", replacements included. Elsewhere, ask the building department before the permit is pulled.

Heat pumps: heating load and balance point

Manual J reports heat loss too. In the Massachusetts report it was 37,892 Btu/h against a 14,546 Btu/h cooling load, 2.6 times larger, and a heat pump's output falls as outdoor temperature drops. The balance point is the outdoor temperature where heat pump output equals the heat loss; below it, backup heat covers the gap. Wrightsoft prints it once real equipment is entered. For cooling mode, ENERGY STAR's design report lets a heat pump in a heating-dominated Condition B climate carry capacity up to the cooling load plus 15,000 Btu/h, so it can be sized closer to its heating load. Heating-first sizing lives on our sister site's heat pump sizing and Manual J guide.

How to get a Manual J

  1. Ask the contractors bidding the job for the full room-by-room report, the software name and the Manual S page, and which three inputs moved the answer most. Our quote comparison worksheet puts it next to the AHRI reference and scope lines.
  2. Hire an independent designer when two bids disagree on size.
  3. Call a HERS rater from RESNET's directory and ask for a blower door test, which turns infiltration from a guess into a measurement.
  4. Run one yourself to learn. A $45 Cool Calc project shows which inputs drive your load.

Whoever does it will need:

  • A floor plan with dimensions, ceiling heights and the direction the front door faces.
  • Every window and glass door by wall direction, with size and the NFRC U-factor and SHGC.
  • Insulation R-values for attic, walls and floors, plus wall and foundation type.
  • Duct, furnace and air handler locations, and any blower door or duct leakage test.
  • Bedroom count and unusual loads, such as a second kitchen.
  • Photos of the attic, windows, ducts and equipment nameplates.

ACCA's HVAC plan review form, updated in 2024, asks for the same items.

Red flags in a contractor's "load calculation"

  • It uses only floor area and climate zone.
  • The output matches a rule of thumb: 500 sq ft per ton, 400 CFM per ton, or total capacity equal to 1.3 times sensible. The ICC lists all three as causes of oversizing.
  • It is a one-page block load for a replacement that changes ducts or registers.
  • Every room receives airflow in proportion to square footage, or the old equipment size is the starting conclusion.
  • Indoor design is 72°F, or outdoor design is hotter than Table 1A.
  • Window orientation and construction are missing.
  • Ducts in a hot attic are treated as if they were inside conditioned space.
  • The report always rounds up "for safety."
  • A "required capacity at 0.70 SHR" line stands in for equipment selection, with no link to the exact equipment's performance.
  • No software name or ACCA approval line appears.

Oversizing is not free insurance. ENERGY STAR warns that oversized equipment may cycle too frequently, reduce comfort, and shorten equipment life, and DOE research links it with higher summer humidity and increased wear; our short cycling guide covers the symptoms.

Block load versus room-by-room load

A block load treats the home as one zone. It can help select total capacity, but the firm behind the Baltimore report notes that block loads "do not provide actual cfm and btu's required for each room." A room-by-room calculation supports duct and register decisions and exposes rooms with unusual glass or envelope problems. For a full replacement, ask for it, and if the existing ducts stay, compare required room airflow with what they can deliver.

How to verify the AHRI match yourself

Manual S selects the equipment; the free AHRI Directory at ahridirectory.org lets you confirm, independently of the contractor, that the outdoor unit, indoor coil or air handler, and furnace (if any) were tested together as a certified matched system.

  1. Search the AHRI Certified Reference Number if the paperwork lists one.
  2. Otherwise enter only the first several characters of the outdoor model number; manufacturers often list shortened model numbers, so a full nameplate string frequently returns nothing.
  3. Narrow with the first characters of the indoor coil or air handler model, and the furnace if there is one.
  4. Find the exact combination installed. A single swapped coil changes the certified rating.
  5. Open the certificate, which lists capacity, SEER2 and EER2, and compare its model numbers with the nameplates and invoice.
AHRI certificateManufacturer spec sheet
What it ratesThe exact outdoor, indoor and furnace combination tested togetherA single component
Efficiency shownOne certified SEER2/EER2 for that pairingOften an "up to" figure across pairings
Verified byAHRI's independent certification programThe manufacturer's own literature
IdentifierAHRI Certified Reference NumberNone tied to an installed pairing

A certificate confirms the pairing and its rating. It does not certify that the tonnage fits your house, that the ducts can deliver it, or that the installation was done well; Manual J, Manual D and commissioning readings cover those. AHRI's advocacy page lists the regional minimums for split-system central air conditioners in effect since January 1, 2023, checked September 20, 2026:

RegionUnder 45,000 Btu/h45,000 Btu/h and upEnforced by
North13.4 SEER213.4 SEER2Date of manufacture
Southeast14.3 SEER213.8 SEER2Date of installation
Southwest14.3 SEER2, 11.7 EER213.8 SEER2, 11.2 EER2Date of installation

When the house has changed

Recalculate after major window replacement, insulation, air sealing, additions, finished basements, roof changes, or duct relocation. Repeating the existing tonnage can preserve an error made for an older version of the house. If planned improvements are not finished, ask for two scenarios rather than pretending they already exist.

Buyer verdict

A capacity number without its assumptions is a guess you cannot audit. Insist on the room-by-room load, the equipment-selection step and an airflow plan, then check the inputs against the tables above. If you already have a proposal, send it for an independent quote review and we will check the capacity basis along with scope and price.

FAQ

How much does a Manual J load calculation cost?

Published prices checked November 10, 2026 run from $45 per project in ACCA-approved Cool Calc software and $100 to $179 for remote reports to $350 at an engineering firm and $795 for an on-site scan. Manual J, S and D packages start at $199 at one remote firm, $520 at a HERS-rater firm and from $990 at an engineering firm.

What does a Manual J report include?

Software and design conditions, every wall, ceiling, floor, door and window with its U-value and SHGC, infiltration, ventilation, duct loads, internal gains, room-by-room loads and airflow, sensible and latent totals, an exposure diversity statement and an equipment summary.

How do I check a Manual J?

Confirm 75°F indoors for cooling and 70°F for heating, ACCA Table 1A outdoor temperatures for the nearest station, bedrooms plus one occupants at 230 Btu/h sensible and 200 latent each, window U and SHGC from NFRC labels, infiltration that matches any blower door test, the real duct location and no safety factor.

Is Manual J required by code?

Where a jurisdiction adopts 2021 IRC Section M1401.3 or IECC R403.7, equipment must be sized with Manual S from Manual J loads. Enforcement varies: Pima County, Arizona rejects plans without Manual J, S and D, including most replacements, while other departments set their own change-out rules.

Can I do a Manual J myself?

Yes, in ACCA-approved Cool Calc for $45 per project, and ACCA's free SpeedSheet covers simple abridged-edition houses. It is a good way to understand the assumptions; equipment selection and duct design should come from a qualified designer.

Does Manual J tell me the AC tonnage?

No. It produces loads. Manual S uses them with the manufacturer's expanded performance data to select equipment, and ENERGY STAR's design report recommends single-stage capacity of 90 to 115 percent of the total load. A "recommended tons" line on a load report is a shortcut, not a selection.

What we could not verify

  • Enforcement on replacements. No national database shows which departments require a Manual J for a change-out.
  • The next edition. ACCA said in November 2025 that a revision is planned for 2026; its Manual J page still listed the 2016 edition on October 16, 2026.
  • Duct gain factors. Manual J's duct tables are not public, so the worked example uses our calculator's 15 percent attic-duct factor.
  • Prices. Wrightsoft and Elite do not publish software prices, and eight price lists are not a market survey.
  • Code text by edition. We read 2021-based state and city adoptions, not the 2024 model codes.
  • The AHRI record. The directory certifies capacity and efficiency, not room airflow, and no consumer tool links an AHRI number to an address.

Sources

Prices checked November 10, 2026; all other sources October 16, 2026 unless noted.