The short answer
Manual J (ANSI/ACCA 2 Manual J-2016, 8th Edition) calculates each room's heat loss and its sensible, latent and total heat gain at local design conditions; Manual S then picks the equipment. Published prices checked November 10, 2026 run from $45 per project in ACCA-approved software and $100 to $179 for a remote report to $350 to $795 at engineering or on-site firms, with Manual J, S and D packages listed from $199 to $990 and up. A sound report uses 75°F indoors for cooling and 70°F for heating, ACCA Table 1A outdoor temperatures, bedrooms plus one occupants at 230 Btu/h sensible and 200 latent each, and no safety factor.
A Manual J load calculation is ACCA's ANSI-recognized method, ANSI/ACCA 2 Manual J-2016 (8th Edition), for working out how much heat each room gains on a design summer day and loses on a design winter night, in sensible, latent and total Btu per hour. Published prices checked November 10, 2026 run from $45 per project in ACCA-approved software you run yourself, through $100 to $179 for a remote report, to $795 for an on-site scan, delivered within hours to 7 business days. Manual J does not choose the air conditioner; Manual S does. A report is only as good as its inputs, so this guide shows what a real one contains and which numbers to check.
Quick answer
| Question | Short answer | Basis |
|---|---|---|
| What is it? | ACCA's residential load standard, 8th Edition, Version 2.50 | ANSI recognition, August 2016 |
| What does it output? | Heat loss plus sensible, latent and total heat gain per room and for the house | ACCA |
| What does it cost? | $45 DIY; $100 to $179 remote; $350 to $795 at engineering or on-site firms | 8 price pages, Nov 10, 2026 |
| J, S and D together? | From $199 remote; $520 at a HERS-rater firm; from $990 at an engineering firm | Same |
| How long? | Same day to 7 business days after plans arrive | Same |
| Required? | Where IRC M1401.3 or IECC R403.7 is adopted; enforcement is local | 2021 IRC, state codes |
| What it does not do | Choose equipment (Manual S) or size ducts (Manual D) | ACCA |
How we built this guide
- The standard: ACCA's Manual J page, its August 9, 2016 release on ANSI recognition, and its November 5, 2025 notice proposing to reaffirm the 2016 edition unchanged.
- Real reports: three reports from ACCA-approved software posted publicly on Green Building Advisor's Q&A forum: an Elite RHVAC report for a 1,537 sq ft Baltimore house (October 2023), and two 2019 Wrightsoft reports, for a 3,203 sq ft Maryland house by Energy Vanguard and a 1,932 sq ft Arlington, Massachusetts house by Bruce Harley Energy Consulting.
- Review checklists: the International Code Council's 2017 CodeNotes on verifying Manual J, ENERGY STAR's National HVAC Design Report Rev. 14 (January 2025), a September 2018 Texas Department of Housing and Community Affairs guide, and December 2022 NYS Clean Heat infiltration guidance.
- Prices and code: eight providers' published price pages, checked November 10, 2026, and the 2021 IRC as adopted in Seattle, Virginia's 2021 code, Washington's energy code and Pima County, Arizona's permit rules, checked October 16, 2026.
We did not commission a Manual J, measure a house or test software.
Manual J, Manual S, and Manual D
| Step | Question it answers | What you should receive |
|---|---|---|
| Manual J | How much heating and cooling does each room need? | Block and room-by-room load summary plus assumptions |
| Manual S | Which actual equipment performs correctly at those conditions? | Selection using OEM expanded performance data |
| Manual D | Can the ducts deliver the required airflow quietly? | Supply and return sizing, airflow, pressure, and register plan |
A "3-ton" unit does not deliver the same capacity under every condition, so Manual S checks real performance against the loads. Watch for shortcut lines: Wrightsoft can print "Req. total capacity at 0.70 SHR", and the Elite report we read printed "Recommended 3.05 tons" from an assumed 75 percent sensible capacity. Energy Vanguard's Allison Bailes calls such lines a guess until a designer has run the equipment's performance data. A real Manual S page names the condenser, coil and AHRI reference.
What a Manual J report includes, section by section
Wrightsoft prints a "Project Summary" or a shorter "Load Short Form"; Elite prints a "Project Report" with "Check Figures". A complete report covers the same ground either way.
| Section | What it shows | What to check |
|---|---|---|
| Project information | Address, date, designer, software and version | Software on ACCA's list; dated after any upgrades |
| Design conditions | Weather station, outdoor dry and wet bulb, indoor temperature and humidity, grains difference | Nearby station; 75°F cooling, 70°F heating |
| Construction | Each wall, ceiling, floor, door and window with area and U-value; SHGC for glass | Matches the house today |
| Infiltration | Method, tightness category, air changes per hour and CFM | Blower door result if one exists |
| Ventilation | Outdoor air CFM from a fan or ERV | Only fans that run continuously |
| Ducts | Location, insulation, leakage, duct gain and loss in Btu/h | Zero only if ducts are indoors |
| Internal gains | Occupants, appliances, lighting | Bedrooms plus one; 1,200 or 2,400 Btu/h appliances |
| Room-by-room table | Heating and cooling load and CFM per room | Every room has an airflow target |
| Building totals | Heat loss, sensible, latent and total gain | Latent shown separately |
| Exposure diversity (AED) | Whether glass load spikes at one hour | Required statement under the 2016 standard |
| Equipment summary | Make, model, AHRI reference, capacities, airflow, static pressure | Filled in, not "n/a", once equipment is quoted |
Two lines need explaining. AED, adequate exposure diversity, covers houses with most glass facing one way: the Elite report allows a peak-hour glass load up to 30 percent above the 12-hour average, and because its house peaked 35.3 percent above the average, the software added a 452 Btu/h "AED excursion". Wrightsoft's rate/swing multiplier, 0.93 to 0.96 in the reports we read, scales the sensible load down. Both are part of the method, not padding.
What three public reports show
| Item | Baltimore, 2023 | Maryland, 2019 | Massachusetts, 2019 |
|---|---|---|---|
| Software | Elite RHVAC | Wrightsoft | Wrightsoft |
| Conditioned area | 1,537 sq ft | 3,203 sq ft | 1,932 sq ft |
| Outdoor design, cool / heat | 89°F / 17°F | 91°F / 17°F | 88°F / 9°F |
| Indoor design | 75°F / 70°F | 75°F / 70°F | 75°F / 70°F |
| Infiltration | Semi-loose, 0.40 ACH | Tight, 0.05 ACH | Average |
| Duct load | 0 Btu/h | 0 Btu/h | Not on short form |
| Total cooling | 33,344 Btu/h | 9,933 Btu/h | 14,546 Btu/h |
| Heat loss | 30,006 Btu/h | 13,146 Btu/h | 37,892 Btu/h |
| Sq ft per ton | 503 | About 3,870 | About 1,590 |
- Two Maryland reports, two weather stations. One used 89°F, the other 91°F at BWI airport. Energy Vanguard treats a couple of degrees as minor and a 5°F gap as an error to fix.
- Internal gains can swing a result. The Baltimore report's equipment line was 10,100 Btu/h sensible, about a third of its cooling load, for a house with two kitchens. Manual J's standard appliance allowance is 1,200 or 2,400 Btu/h.
- A short form is not enough to audit. The Massachusetts summary shows no U-values, infiltration rate or duct line. The Texas guide warns that construction pages may not come with a report unless you ask.
How to check a Manual J: 15 points
The ICC's CodeNotes ranks inputs by effect: design temperatures first, then windows and glass doors, ducts, and ceilings under an attic. Infiltration and ventilation sit in the middle; insulated walls and floors and internal gains matter least.
Design conditions and internal gains
| Input | What it should say | Red flag |
|---|---|---|
| Indoor cooling | 75°F at 50% RH (45% dry climate, 55% humid) | 72°F or lower |
| Indoor heating | 70°F | Higher than 70°F |
| Outdoor cooling | ACCA Table 1A 1% value, nearest station | 5°F or more above it |
| Outdoor heating | Table 1A 99% value | Colder than the table |
| Occupants | Bedrooms plus one | More, without a stated reason |
| People load | 230 Btu/h sensible, 200 latent each | Higher per-person values |
| Appliances | 1,200 or 2,400 Btu/h, or an itemized list | A large unexplained number |
Table 1A values for 15 cities, from Phoenix's 108°F to Seattle-Tacoma's 81°F, are in our AC sizing guide; ACCA says to use them as published, with no safety factor. Occupants matter too: Energy Vanguard found 23 people entered for a five-bedroom house, and at 430 Btu/h each the 17 extra people added about 7,300 Btu/h, more than half a ton.
Envelope, air leakage and ducts
| Input | What it should say | Red flag |
|---|---|---|
| Window area | Total and direction match the plans | More than 15 sq ft under or 60 sq ft over |
| Window U and SHGC | Values from the NFRC label | Single-pane values for low-e glass, or the reverse |
| Ceiling, wall, floor R | What is installed today | Planned upgrades entered as done |
| Infiltration | Blower door based, or a matching category | "Loose" on a house that tested tight |
| Floor area | Within 10% of the real conditioned area | Garage or unconditioned rooms counted |
| Duct location | Where the ducts actually run | Attic ducts modeled as indoors, or the reverse |
| Duct tightness | "Average sealed" or tighter | Default leaky ducts after sealing work |
| Safety factor | None | A percentage added to the total |
The window tolerance is ENERGY STAR's; its design report also wants occupants within 2 of the real count and the predominant SHGC within 0.1. The 10 percent floor-area check is Pima County's rule for replacement permits.
NFRC labels print each window's U-factor and SHGC. The Texas guide puts single-pane glass at a U-value of about 1.22, and the Baltimore report entered clear double-pane vinyl windows at U 0.57 and SHGC 0.56. ENERGY STAR's current criteria show what newer windows carry:
| ENERGY STAR zone | U-factor | SHGC |
|---|---|---|
| Northern | 0.22 or less | 0.17 or more |
| North-Central | 0.25 or less | 0.40 or less |
| South-Central | 0.28 or less | 0.23 or less |
| Southern | 0.32 or less | 0.23 or less |
In the reports we read, infiltration was picked from a menu. Manual J's Table 5A sets default air changes per hour for five categories, with the range depending on house size:
| Manual J category | Cooling ACH | Heating ACH | Blower door match |
|---|---|---|---|
| Tight | 0.05 to 0.11 | 0.10 to 0.21 | About 3 ACH50, a code-level house |
| Semi-tight | 0.10 to 0.22 | 0.19 to 0.41 | About 3 ACH50 |
| Average | 0.15 to 0.35 | 0.28 to 0.61 | About 9 ACH50 |
| Semi-loose | 0.23 to 0.50 | 0.43 to 0.95 | Not mapped |
| Loose | 0.30 to 0.67 | 0.58 to 1.29 | Not mapped |
The blower door column is NYS Clean Heat's 2022 comparison. If the house has been tested, ask for the measured number, as Energy Vanguard recommends; without a test, Pima County expects replacement jobs to use average, semi-loose or loose.
For ducts, ENERGY STAR says about 20 to 30 percent of the air moving through a typical system is lost to leaks and poor connections. Both full reports we read carried a duct load of 0 Btu/h, which is right only when ducts sit inside conditioned space; attic ducts should show a duct gain. Our ductwork guide covers the measurements.
The bottom-line checks
- No safety factor. Manual S already lets single-stage equipment carry 90 to 115 percent of the load, so padding the load double-counts.
- Square feet per ton. Energy Vanguard's 40 recent designs, mostly in the Southeast, averaged 1,431 sq ft per ton, the lowest 624, so a new code-built house near 500 deserves a second look. Existing homes carry higher loads; our screening ranges for them run 430 to 750.
- The old unit. The Texas guide tells weatherization staff to investigate any result larger than the system being replaced.
Worked example: where the load comes from in an 1,800 sq ft house
This is an illustration built from published Manual J factors, not a Manual J result. The house is one story with 8-foot ceilings, three bedrooms, 270 sq ft of clear double-pane windows (15 percent of the floor), 40 sq ft of doors and 1,130 sq ft of net wall. Design conditions match the Baltimore report: 89°F outdoors, 75°F indoors, a 50-grain moisture difference.
Window, wall and door factors are that report's loads per square foot (its walls are insulated brick). The ceiling row applies its effective 49°F temperature difference (657 Btu/h through 670.6 sq ft of R-50 ceiling at U 0.02) to R-30 and R-19. Air leakage uses the report's 1.1 and 0.68 multipliers with Table 5A air changes, and the attic-duct row uses the 15 percent factor in our sizing calculator because Manual J's duct tables are not public.
| Component | Tighter house | Leakier house | Factor used |
|---|---|---|---|
| Windows, 270 sq ft | 12,800 | 12,800 | 47.4 Btu/h per sq ft |
| Walls, 1,130 sq ft | 900 | 900 | 0.82 per sq ft |
| Doors, 40 sq ft | 400 | 400 | 9.7 per sq ft |
| Ceiling, 1,800 sq ft | 2,900 (R-30) | 4,600 (R-19) | U x 49°F |
| Air leakage, sensible | 1,100 (0.30 ACH) | 1,700 (0.45 ACH) | 1.1 x CFM x 14°F |
| Ducts | 0 (indoors) | 3,400 (attic) | 15% of sensible |
| People, 4 | 920 | 920 | 230 each |
| Appliances | 1,200 | 1,200 | Manual J allowance |
| Sensible total | 20,220 | 25,920 | |
| Air leakage, latent | 2,400 | 3,700 | 0.68 x CFM x 50 grains |
| People, latent | 800 | 800 | 200 each |
| Total cooling | 23,420 | 30,420 | |
| Tons | 1.95 | 2.53 | Total divided by 12,000 |
All loads are in Btu/h. Windows dominate: 55 percent of the tighter house's load and 42 percent of the leakier one's. The leakier house's ceiling, air leakage and attic ducts add 7,000 Btu/h between them, more than half a ton. Both come out at a sensible heat ratio of about 0.85, inside the 0.8 to 0.9 Energy Vanguard reports for eastern North America. The same arithmetic shows how input choices move the answer:
- Outdoor design 5°F hotter: about 2,000 Btu/h more sensible load in the tighter house.
- Indoor design of 72°F instead of 75°F: about 1,200 Btu/h more sensible load, plus more latent load.
- 10,100 Btu/h of equipment instead of 1,200: 8,900 Btu/h more, about three-quarters of a ton.
Both totals sit below the 3.3 to 4.3 tons our calculator screens for an average 1,800 sq ft house in the hot-humid state group that includes Maryland. A screening range has to cover houses it cannot see; a component load covers one house. Reuse the method, not the number.
What a Manual J costs in 2026
No federal agency publishes Manual J prices; these are the price lists we found, checked November 10, 2026.
| Option | Published price | What you get | Turnaround |
|---|---|---|---|
| DIY, Cool Calc | $45 per project | J, S and D in approved software | Your own pace |
| Remote, EnergyReports.net | J, S and D from $199 | Priced by size and systems | Not stated |
| Remote J and S, B&B System Design | $100 block, $140 room-by-room under 2,000 sq ft | Wrightsoft, one system | 3 to 4 days |
| Remote J, Manual J Calculator | $109 block, $179 room-by-room to 2,900 sq ft | $0.10 per extra sq ft | 48 hours with $100 deposit |
| HERS raters, REScheckReview | $129 J, $89 S | To 6,000 sq ft | Often within hours |
| HERS raters, TLC Inspectors | $370 J and S; $520 J, S and D | To 2,000 sq ft | 2 to 7 business days |
| Engineering firm, LoadCalculationsHVAC | $0.14 per sq ft, $350 minimum; J, S and D from $990 | Wrightsoft, duct layout on plans | 24 to 48 hours |
| On-site scan, HVAC Inspections Los Angeles | $795 to 2,500 sq ft; $995 to 4,000 | LiDAR scan, room-by-room report | Set at booking |
| Contractor bidding the job | Varies | Ask for the full report | With the bid |
For an 1,800 sq ft house, a room-by-room Manual J from these lists costs $140 to $795. Remote services model what you send, so their accuracy depends on your plans; an on-site scan measures the house. Against the $6,000 to $9,800 standard-tier band for a 3-ton replacement, $140 to $520 is about 1.4 to 8.7 percent of the job, while going a full ton too big adds $1,500 to $2,700 at standard tier before any circuit or duct changes.
ACCA-approved software and free tools
ACCA keeps the official list and says plainly: "If software is not listed on this page, then it is not ACCA-approved." The Texas weatherization program's 2018 guidance requires approved software on every job it funds.
| Software | ACCA status | Price found | Notes |
|---|---|---|---|
| Wrightsoft Right-J8 | Full Manual J | Not published | Used by two firms above |
| Elite RHVAC | Full Manual J | Not published | Prints sq ft per ton |
| Cool Calc Manual J | Full Manual J | $45 per project; $50 per user a month | Browser or LiDAR iPad |
| Acculoads, EnergyGauge, HVAC ResLoad-J, HeatCAD and LoopCAD MJ8, Conduit Tech, Amply Energy, Zero Homes | Full Manual J | Not checked | Conduit Tech powers the LA scan |
| Right-J Mobile, CalcuNow MJ8-Calc | Block load only | Not checked | No room airflow |
| ACCA Manual J8 AE SpeedSheet | ACCA's own Excel sheet | Free; needs the manual | Abridged cases only |
| LoadCalc.net | Not approved | Free | "Not accredited by any organization" |
Pima County sums up the SpeedSheet's abridged cases as one zone, glass under 15 percent of floor area, a dark shingle roof and ducts indoors. For a permit or a quote dispute, use an approved program.
Is Manual J required by code?
The 2021 International Residential Code, Section M1401.3, says equipment "shall be sized in accordance with ACCA Manual S" based on loads "calculated in accordance with ACCA Manual J", or other approved methods. Two exceptions let multistage or variable-refrigerant-flow equipment exceed Manual S limits when the loads fall within its published capacity range, and allow the next larger standard size when no unit meets both the total and sensible loads. IECC R403.7 repeats the rule in the energy code, and M1601.1 sends duct design to Manual D.
| Code or jurisdiction | What it says | Replacements |
|---|---|---|
| 2021 IRC M1401.3 | Manual S sizing from Manual J loads; two exceptions | Where the local code applies it |
| Washington, R403.7 | No larger than the smallest size that covers the load within oversizing limits | Not stated in the section |
| Virginia, 2021 code | J, S and D required since the 2009 edition; a third exception for the maker's smallest unit | Not stated |
| Pima County, Arizona | J, S and D with the plans; capacity within 6,000 Btu/h of the sensible load | Yes, unless in a utility program |
| ENERGY STAR new homes | Unabridged Manual J 8 and the Rev. 14 design report | New homes only |
Pima County is the clearest enforcement example we found: plans without the calculations "will not be accepted for review", replacements included. Elsewhere, ask the building department before the permit is pulled.
Heat pumps: heating load and balance point
Manual J reports heat loss too. In the Massachusetts report it was 37,892 Btu/h against a 14,546 Btu/h cooling load, 2.6 times larger, and a heat pump's output falls as outdoor temperature drops. The balance point is the outdoor temperature where heat pump output equals the heat loss; below it, backup heat covers the gap. Wrightsoft prints it once real equipment is entered. For cooling mode, ENERGY STAR's design report lets a heat pump in a heating-dominated Condition B climate carry capacity up to the cooling load plus 15,000 Btu/h, so it can be sized closer to its heating load. Heating-first sizing lives on our sister site's heat pump sizing and Manual J guide.
How to get a Manual J
- Ask the contractors bidding the job for the full room-by-room report, the software name and the Manual S page, and which three inputs moved the answer most. Our quote comparison worksheet puts it next to the AHRI reference and scope lines.
- Hire an independent designer when two bids disagree on size.
- Call a HERS rater from RESNET's directory and ask for a blower door test, which turns infiltration from a guess into a measurement.
- Run one yourself to learn. A $45 Cool Calc project shows which inputs drive your load.
Whoever does it will need:
- A floor plan with dimensions, ceiling heights and the direction the front door faces.
- Every window and glass door by wall direction, with size and the NFRC U-factor and SHGC.
- Insulation R-values for attic, walls and floors, plus wall and foundation type.
- Duct, furnace and air handler locations, and any blower door or duct leakage test.
- Bedroom count and unusual loads, such as a second kitchen.
- Photos of the attic, windows, ducts and equipment nameplates.
ACCA's HVAC plan review form, updated in 2024, asks for the same items.
Red flags in a contractor's "load calculation"
- It uses only floor area and climate zone.
- The output matches a rule of thumb: 500 sq ft per ton, 400 CFM per ton, or total capacity equal to 1.3 times sensible. The ICC lists all three as causes of oversizing.
- It is a one-page block load for a replacement that changes ducts or registers.
- Every room receives airflow in proportion to square footage, or the old equipment size is the starting conclusion.
- Indoor design is 72°F, or outdoor design is hotter than Table 1A.
- Window orientation and construction are missing.
- Ducts in a hot attic are treated as if they were inside conditioned space.
- The report always rounds up "for safety."
- A "required capacity at 0.70 SHR" line stands in for equipment selection, with no link to the exact equipment's performance.
- No software name or ACCA approval line appears.
Oversizing is not free insurance. ENERGY STAR warns that oversized equipment may cycle too frequently, reduce comfort, and shorten equipment life, and DOE research links it with higher summer humidity and increased wear; our short cycling guide covers the symptoms.
Block load versus room-by-room load
A block load treats the home as one zone. It can help select total capacity, but the firm behind the Baltimore report notes that block loads "do not provide actual cfm and btu's required for each room." A room-by-room calculation supports duct and register decisions and exposes rooms with unusual glass or envelope problems. For a full replacement, ask for it, and if the existing ducts stay, compare required room airflow with what they can deliver.
How to verify the AHRI match yourself
Manual S selects the equipment; the free AHRI Directory at ahridirectory.org lets you confirm, independently of the contractor, that the outdoor unit, indoor coil or air handler, and furnace (if any) were tested together as a certified matched system.
- Search the AHRI Certified Reference Number if the paperwork lists one.
- Otherwise enter only the first several characters of the outdoor model number; manufacturers often list shortened model numbers, so a full nameplate string frequently returns nothing.
- Narrow with the first characters of the indoor coil or air handler model, and the furnace if there is one.
- Find the exact combination installed. A single swapped coil changes the certified rating.
- Open the certificate, which lists capacity, SEER2 and EER2, and compare its model numbers with the nameplates and invoice.
| AHRI certificate | Manufacturer spec sheet | |
|---|---|---|
| What it rates | The exact outdoor, indoor and furnace combination tested together | A single component |
| Efficiency shown | One certified SEER2/EER2 for that pairing | Often an "up to" figure across pairings |
| Verified by | AHRI's independent certification program | The manufacturer's own literature |
| Identifier | AHRI Certified Reference Number | None tied to an installed pairing |
A certificate confirms the pairing and its rating. It does not certify that the tonnage fits your house, that the ducts can deliver it, or that the installation was done well; Manual J, Manual D and commissioning readings cover those. AHRI's advocacy page lists the regional minimums for split-system central air conditioners in effect since January 1, 2023, checked September 20, 2026:
| Region | Under 45,000 Btu/h | 45,000 Btu/h and up | Enforced by |
|---|---|---|---|
| North | 13.4 SEER2 | 13.4 SEER2 | Date of manufacture |
| Southeast | 14.3 SEER2 | 13.8 SEER2 | Date of installation |
| Southwest | 14.3 SEER2, 11.7 EER2 | 13.8 SEER2, 11.2 EER2 | Date of installation |
When the house has changed
Recalculate after major window replacement, insulation, air sealing, additions, finished basements, roof changes, or duct relocation. Repeating the existing tonnage can preserve an error made for an older version of the house. If planned improvements are not finished, ask for two scenarios rather than pretending they already exist.
Buyer verdict
A capacity number without its assumptions is a guess you cannot audit. Insist on the room-by-room load, the equipment-selection step and an airflow plan, then check the inputs against the tables above. If you already have a proposal, send it for an independent quote review and we will check the capacity basis along with scope and price.
FAQ
How much does a Manual J load calculation cost?
Published prices checked November 10, 2026 run from $45 per project in ACCA-approved Cool Calc software and $100 to $179 for remote reports to $350 at an engineering firm and $795 for an on-site scan. Manual J, S and D packages start at $199 at one remote firm, $520 at a HERS-rater firm and from $990 at an engineering firm.
What does a Manual J report include?
Software and design conditions, every wall, ceiling, floor, door and window with its U-value and SHGC, infiltration, ventilation, duct loads, internal gains, room-by-room loads and airflow, sensible and latent totals, an exposure diversity statement and an equipment summary.
How do I check a Manual J?
Confirm 75°F indoors for cooling and 70°F for heating, ACCA Table 1A outdoor temperatures for the nearest station, bedrooms plus one occupants at 230 Btu/h sensible and 200 latent each, window U and SHGC from NFRC labels, infiltration that matches any blower door test, the real duct location and no safety factor.
Is Manual J required by code?
Where a jurisdiction adopts 2021 IRC Section M1401.3 or IECC R403.7, equipment must be sized with Manual S from Manual J loads. Enforcement varies: Pima County, Arizona rejects plans without Manual J, S and D, including most replacements, while other departments set their own change-out rules.
Can I do a Manual J myself?
Yes, in ACCA-approved Cool Calc for $45 per project, and ACCA's free SpeedSheet covers simple abridged-edition houses. It is a good way to understand the assumptions; equipment selection and duct design should come from a qualified designer.
Does Manual J tell me the AC tonnage?
No. It produces loads. Manual S uses them with the manufacturer's expanded performance data to select equipment, and ENERGY STAR's design report recommends single-stage capacity of 90 to 115 percent of the total load. A "recommended tons" line on a load report is a shortcut, not a selection.
What we could not verify
- Enforcement on replacements. No national database shows which departments require a Manual J for a change-out.
- The next edition. ACCA said in November 2025 that a revision is planned for 2026; its Manual J page still listed the 2016 edition on October 16, 2026.
- Duct gain factors. Manual J's duct tables are not public, so the worked example uses our calculator's 15 percent attic-duct factor.
- Prices. Wrightsoft and Elite do not publish software prices, and eight price lists are not a market survey.
- Code text by edition. We read 2021-based state and city adoptions, not the 2024 model codes.
- The AHRI record. The directory certifies capacity and efficiency, not room airflow, and no consumer tool links an AHRI number to an address.
Sources
Prices checked November 10, 2026; all other sources October 16, 2026 unless noted.
- ACCA: Manual J Residential Load Calculation, ANSI/ACCA 2 Manual J-2016
- ACCA: 2016 Manual J recognized by ANSI, August 9, 2016
- ACCA: ANSI public review for reaffirmation of Manual J-2016, November 5, 2025
- ACCA Outdoor Design Conditions Guide, Manual J 8th Edition Tables 1A and 1B, 2014
- ACCA: Approved software list
- ACCA: SpeedSheet for Manual J Abridged Edition
- ACCA: Residential system design review forms and examples, HVAC plan review 2024
- ACCA: Manual S Residential Equipment Selection
- ICC CodeNotes: Verifying ACCA Manual J Procedures, 2017
- ENERGY STAR National HVAC Design Report, Rev. 14, January 15, 2025
- ENERGY STAR: HVAC quality installation
- ENERGY STAR: Duct sealing
- ENERGY STAR: Certification criteria for residential windows, October 2023
- NFRC: Residential product certification and the energy performance label
- Texas Department of Housing and Community Affairs: Accuracy checks on Manual J calculations, September 2018
- NYS Clean Heat: Infiltration guidance for buildings at design conditions, December 20, 2022
- Three Manual J reports from ACCA-approved software posted publicly on Green Building Advisor's Q&A forum: an Elite RHVAC report for a 1,537 sq ft Baltimore house (October 2023), an Energy Vanguard Wrightsoft summary for a 3,203 sq ft Maryland house (September 2019) and a Bruce Harley Energy Consulting Wrightsoft short form for an Arlington, Massachusetts house (October 2019). We do not link the files because they show homeowners' names and contact details.
- Energy Vanguard: How to read Manual J load calculation reports, May 21, 2018
- Energy Vanguard: Air conditioner sizing rules of thumb must die, August 26, 2016
- 2021 Seattle Residential Code, Chapter 14, Section M1401.3
- Viridiant: Heating and cooling design requirements, 2021 Virginia residential code guide, 2025
- Washington Administrative Code 51-11R-40360, Section R403.7 equipment sizing, effective July 1, 2023
- Pima County, Arizona: HVAC sizing requirements
- RESNET: Rating company directory
- Cool Calc: Manual J, S and D pricing
- LoadCalc.net: free online load calculation and disclaimer
- Manual J Calculator: published load calculation prices
- B&B System Design: Manual JS pricing
- EnergyReports.net: Manual J, S and D pricing
- REScheckReview: Manual J and Manual S pricing
- TLC Inspectors: Manual J, S and D report pricing
- LoadCalculationsHVAC: Manual J and design package pricing
- HVAC Inspections Los Angeles: on-site Manual J pricing
- U.S. Department of Energy, HVAC Sizing Research, February 12, 2016
- AHRI Directory of Certified Product Performance
- AHRI: AHRI Directory
- AHRI Support: Staff tips for successful directory searches
- AHRI: Residential central air conditioners, regional efficiency standards, checked September 20, 2026
How this guide is checked
Written by Air Conditioner Guide Editorial Team. Editorial review by Air Conditioner Guide Editorial Team, last reviewed October 16, 2026. We check the sizing logic, quote-scope claims, and sources. No affiliate ranking bias.
Have a proposal?
Check the quote before you sign.
We'll look at the model match, capacity basis, install scope, warranty, and missing questions. Free, independent, no lead auction.
Check my quoteRelated guides

What Size AC Do I Need? 2026 Sizing Chart and Manual J Check
Screening AC tonnage by home size and climate for 2026, why square footage alone fails, and how Manual J and Manual S set the final size.
Read the guide
AC Condensate Drain Clogged? Fixes, Code and 2026 Costs
A clogged AC condensate drain costs $75 to $250 to clear. Signs, safe DIY steps, IRC float switch and trap rules, plus pump and water damage costs.
Read the guide
AC Line Set Reuse: 2026 Sizes, Costs and the A2L Rules
Can you reuse an AC line set? Sizes by tonnage from four manufacturers, R-454B, R-32 and R-22 reuse rules, the test steps and 2026 replacement costs.
Read the guide