The short answer
Central AC needs an indoor coil and a blower. Homes with a gas furnace use the furnace blower plus a cased evaporator coil, which sits inside our $6,000 to $9,800 standard-tier 3-ton band, while homes without one use an air handler, which adds $1,500 to $3,500 and often carries electric heat strips on a 25 to 60 amp circuit, or two circuits at 15 kW and up. The SEER2 rating belongs to the certified outdoor and indoor combination, so a new R-454B or R-32 system needs a matched new coil or air handler, not the old one.
Every central air conditioner needs two things indoors: an evaporator coil to pull heat and moisture out of the air, and a blower to move that air across the coil and through the ducts. In a home with a gas furnace, the furnace blower does the pushing and a cased coil sits on top of it. In a home without a furnace, an air handler holds both the blower and the coil in one cabinet, often with electric heat strips for winter. Either way, the indoor half is part of the rated system, and on a 2026 R-454B or R-32 installation it has to be new and matched to the outdoor unit.
Quick answer by home situation
| Your home | What cools it indoors | What changes when the AC is replaced |
|---|---|---|
| Gas or propane furnace | Furnace blower plus a cased evaporator coil | New matched coil, inside our 3-ton band of $6,000 to $9,800 |
| No furnace, electric heat | Air handler with coil, blower and heat strips | New air handler adds $1,500 to $3,500 |
| Heat pump already | Air handler, sometimes with strips as backup | New matched air handler when the refrigerant changes |
| Furnace older than 15 years | Furnace blower plus coil | Price furnace and coil together: adds $3,000 to $7,000 |
| Oil furnace | Furnace blower plus coil | Coil needs a high-temperature drain pan near the heat exchanger |
| Packaged unit on a roof or slab | Coil and blower live in the outdoor cabinet | No indoor coil to match |
Dollar figures are this site's 3-ton cost model bands, data version 2026-07-10, the same ones in our 3-ton central AC cost guide. The oil row is from the Goodman and Daikin coil manual: no plastic pan on oil furnaces or anywhere the pan may exceed 300°F.
How we built this guide
- Rules: 10 CFR 430.32 and 429.16, DOE's January 7, 2025 test procedure rule, DOE's 2014 furnace fan rule, AHRI's type definitions, and all 28 AHRI certificates for one 3-ton outdoor unit.
- Equipment: installation manuals and product data from Goodman and Daikin (2024), Trane (November 2025) and Lennox (June 2025), because they state circuits, airflow and leak-sensor rules in numbers.
- Costs: our cost model for every AC-replacement band, so the numbers match our other guides. Component prices come from This Old House, Fixr and Carrier's 2026 guides, each row dated.
- Electricity: EIA's US residential average of 18.31 cents per kWh for July 2026, released September 24, 2026.
- Limits: no equipment testing and no contractor survey. Everything was checked October 16, 2026.
What an evaporator coil is
The evaporator coil is your air conditioner's indoor heat exchanger. Liquid refrigerant enters through a metering device, a thermal expansion valve (TXV) or a fixed piston, boils inside the tubes and absorbs heat from the air crossing the fins. The air cools below its dew point, so water condenses and drips into a drain pan. The coil is also your dehumidifier, which is why every coil needs a drain.
An A-coil is shaped like an upside-down V, an N-coil or Z-coil folds more surface into a shorter cabinet, and a slab coil is one flat panel. A cased coil has its own metal cabinet that bolts onto a furnace; an uncased coil slides into an existing plenum. This Old House puts coil life at 10 to 15 years with proper maintenance (updated April 6, 2026).
How each setup works
| Part | Furnace plus coil | Air handler |
|---|---|---|
| Blower | Inside the furnace, below or beside the coil | Inside the air handler cabinet |
| Coil | Separate cased coil on the furnace outlet | Built into the same cabinet |
| How air passes the coil | Blown through it | Pulled through it |
| Heat source | Gas, propane or oil burner | Electric heat strips, a heat pump, or both |
| Rating category | AHRI coil-only, or coil with the furnace blower | AHRI coil with blower |
| Electrical | 120-volt furnace circuit | 208/240-volt circuit, larger with strips |
Goodman and Daikin's July 2024 coil manual says coils "must be installed downstream (discharge air) of the furnace." Because an air handler pulls air through its coil and a furnace pushes it through, one drain pan sits under suction and the other under pressure, and each needs the trap its manual specifies; see our condensate drain guide.
Where the equipment sits
| Position | Typical location | Notes |
|---|---|---|
| Upflow | Basement or utility closet | Air enters at the bottom, coil on top |
| Downflow | Main-floor closet, garage, some attics | Air exits at the bottom, coil underneath |
| Horizontal | Attic or crawlspace | Coil on the end; secondary pan matters most here |
| Multi-position | Any of the above | One cabinet set up on site |
Carrier says downflow units are "typically found in attics, garages, or utility closets on the main floor" and horizontal ones are common "in attics or crawl spaces where vertical height is limited." Goodman's AMST air handlers install upflow, downflow, horizontal left or horizontal right, and Trane lists its 5TEMC models for a closet, utility room, alcove, basement, crawlspace or attic.
Do you need a furnace for central air?
No. Central air needs a coil and a blower indoors, and a furnace is only one way to supply the blower. Homes without gas heat use an air handler, and a packaged unit on the roof or a slab holds the coil and blower outdoors. What you cannot do is run a split system on its outdoor unit alone: a quote that names only the condenser is either reusing your coil or incomplete.
What the indoor choice costs in 2026
Component prices first, from named and dated guides. None is a national average; no federal agency publishes one.
| Scope | Installed price | Source and date |
|---|---|---|
| Evaporator coil, 3-ton | $700 to $2,350, average $1,550 | This Old House, Apr 6, 2026 |
| Evaporator coil | $550 to $2,500 | Fixr, Jan 21, 2026 |
| Air handler, 3 to 3.5 tons | $2,000 to $3,000 | Carrier 2026 guide, citing HomeAdvisor |
| Air handler, variable-speed | $2,800 to $4,200 | Carrier 2026 guide, citing HomeAdvisor |
| Air handler replacement | $1,500 to $3,500 | Fixr, Jan 21, 2026 |
| Gas furnace, alone | $3,800 to $10,000 | Carrier 2026 guide, citing Angi |
| Electric furnace, alone | $2,000 to $7,000 | Carrier 2026 guide, citing Angi |
| Blower motor replacement | $300 to $1,000 | Fixr, Jan 21, 2026 |
| Electric heat strips | No verified installed price | See What we could not verify |
What each indoor path adds to a 3-ton AC replacement, from our cost model, which already counts a matched coil in the base band:
| Indoor scope with a new 3-ton AC | Model add | Standard-tier total |
|---|---|---|
| Matched coil on your existing furnace | $0, included | $6,000 to $9,800 |
| New air handler instead of a coil | $1,500 to $3,500 | $7,500 to $13,300 |
| New furnace and coil in the same job | $3,000 to $7,000 | $9,000 to $16,800 |
| New circuit for heat strips, if needed | $400 to $1,800 | Add to the row above |
Better-tier equipment adds $1,200 to $3,000 to each total and premium variable-capacity equipment $3,500 to $7,000. The furnace add sits below Carrier's $3,800 to $10,000 for a furnace alone because the crew, permit, removal and coil are already in the AC band: two separate jobs run $9,800 to $19,800, one combined job $9,000 to $16,800. Rebuild the totals for your scope with the AC sizing and cost calculator.
The matched-system rule
The SEER2 on your quote is not a property of the outdoor unit. It is certified for one combination of outdoor unit, indoor coil or air handler, and sometimes a named furnace, listed in the AHRI Directory. Goodman's air handler and coil manuals both say "installation of unmatched systems is not permitted." AHRI uses two main types:
- RCU-A-C: "Split System: Air-Cooled Condensing Unit, Coil Alone." A coil going on a furnace not named in the rating.
- RCU-A-CB: "Split System: Air-Cooled Condensing Unit, Coil with Blower." An air handler, or a coil certified with one specific furnace, since that furnace supplies the blower.
DOE's coil-only floor
Under 10 CFR 429.16, every single-stage or two-stage outdoor unit needs at least one coil-only rating "representative of the least efficient combination distributed in commerce." Under 10 CFR 430.32(c), that least efficient combination "must be a coil-only combination" and must meet the regional standard, and an outdoor model with any certified combination below that standard "cannot be installed in that region." Variable-capacity outdoor units must have every combination rated instead.
The minimums since January 1, 2023 are 13.4 SEER2 in the North and 14.3 SEER2 in the Southeast and Southwest for systems under 45,000 Btu/h, plus 11.7 EER2 in the Southwest (9.8 EER2 for systems rated 15.2 SEER2 or higher). So a coil-only rating at 13.4 keeps that outdoor model out of the South entirely, even when a blower-coil match reaches 14.3.
One 3-ton outdoor unit, 28 ratings
MRCOOL publishes all 28 AHRI certificates for its 3-ton HAC13036FA outdoor unit, issued December 12, 2024. Grouped by indoor match:
| Indoor match | AHRI type | SEER2 | Capacity at 95°F |
|---|---|---|---|
| Coil only, 10 coils | RCU-A-C | 13.40 for all 10 | 33,600 to 34,400 Btu/h |
| Air handler, 5 models | RCU-A-CB | 13.40 to 14.30 | 33,600 to 35,200 Btu/h |
| Coil plus named furnace, 13 pairs | RCU-A-CB | 13.40 to 14.30 | 33,000 to 34,400 Btu/h |
The same HCMP4248CFOA coil rates 13.40 SEER2 alone and 14.30 with the MGA80EE080C4B furnace, and every certificate lists the North region only: the coil-only floor rule at work. Capacity lands at 92 to 98 percent of the nominal 36,000 Btu/h.
Why the furnace matters: a coil-only test has no blower to measure, so DOE's January 7, 2025 rule assigns a default of 441 watts per 1,000 standard cfm for a conventional single-stage system, about 529 watts at a 3-ton airflow of 1,200 cfm. A blower-coil test measures the real blower at a minimum external static pressure of 0.5 inch of water column. All else equal, a blower that draws less than the default earns a higher rating.
Why an old coil on a new outdoor unit is a red flag
An old R-410A coil under a new outdoor unit is a problem for four reasons:
- The refrigerant changed. Split systems made since January 1, 2025 must use a refrigerant with a global warming potential under 700, which on current equipment means R-454B or R-32. Goodman's coil is "approved for use with R32 refrigerant only," and Trane's R-454B air handlers ship with an R-454B expansion valve.
- The metering device must match. Goodman tells installers to confirm the piston "is rated for use with the outdoor matchup." An old R-410A valve is not.
- New coils carry a leak sensor wired to the furnace board or a Non-A2L Furnace Integration Kit. An old coil has none.
- No AHRI certificate exists for the pair, so nobody can state its SEER2 or prove regional compliance.
EPA does not force out a working R-410A system: "components used to repair existing systems are not subject to these restrictions," and systems built entirely from pre-2025 components have no installation deadline (page updated August 28, 2026). Our R-454B vs R-410A guide covers the repair path.
Blower motors: PSC, constant torque and variable speed
Three blower motor types are in the field:
| Motor | How it behaves | Energy, per DOE |
|---|---|---|
| PSC (permanent split capacitor) | Fixed speed taps; airflow falls as duct resistance rises | Baseline in DOE's furnace fan rule |
| Constant-torque brushless ("X13") | Holds torque on a set tap; airflow still drops at high static | About 41% lower fan energy rating than PSC |
| Constant-airflow brushless ("ECM") | Ramps up to hold the programmed cfm | About 51% lower with multi-stage operation |
The percentages are DOE's estimates of the cut in fan energy rating (FER) from a PSC baseline, in its July 3, 2014 final rule (Table IV.9). FER limits apply to furnace fans made on and after July 3, 2019. A non-weatherized condensing gas furnace with a 1,600 cfm maximum may not exceed about 265 watts per 1,000 cfm (0.044 times 1,600, plus 195). Air handlers sold as central AC or heat pump indoor units are outside the FER table; their blower energy is counted in SEER2 instead.
What duct resistance does to blower watts
Trane's November 2025 product data for its 5TEMCD04AV31DA variable-speed air handler shows the effect at the 3-ton, 400 cfm per ton setting:
| External static pressure | Constant-airflow mode | Constant-torque mode |
|---|---|---|
| 0.1 inch | 1,184 cfm at 160 W | 1,317 cfm at 180 W |
| 0.3 inch | 1,187 cfm at 215 W | 1,207 cfm at 209 W |
| 0.5 inch | 1,193 cfm at 275 W | 1,110 cfm at 233 W |
| 0.7 inch | 1,180 cfm at 325 W | 1,024 cfm at 251 W |
| 0.9 inch | 1,190 cfm at 380 W | 945 cfm at 268 W |
Raising static pressure from 0.1 to 0.9 inch, which is what restrictive ducts and dirty filters do, raised blower power 2.4 times, from 160 W to 380 W, for the same air. In torque mode, airflow fell from 1,317 to 945 cfm; Trane notes that "torque mode will reduce airflow when static is above approximately 0.3-inch water column." At 18.31 cents, 1,000 blower hours cost about $50 at 275 W and about $97 at DOE's 529 W coil-only default. That is arithmetic, not a bill forecast. Ask for a static pressure reading at startup.
Electric heat strips: sizes, circuits and running cost
Air handlers in homes without gas often carry electric resistance heaters, called heat strips or a heat kit. Each kW of strip gives 3,412 Btu per hour. Trane's November 2025 data for the 5TEMCD04AV31DA lists:
| Kit, nominal | Output at 240 V | Circuit: MCA / max breaker | Cost per hour |
|---|---|---|---|
| 4 kW | 3.84 kW, 13,100 Btu/h | 25 A / 25 A | $0.70 |
| 5 kW | 4.80 kW, 16,400 Btu/h | 30 A / 30 A | $0.88 |
| 8 kW | 7.68 kW, 26,200 Btu/h | 45 A / 45 A | $1.41 |
| 10 kW | 9.60 kW, 32,800 Btu/h | 55 A / 60 A | $1.76 |
| 15 kW | 14.4 kW, about 49,100 Btu/h | Two circuits: 55/60 A and 25/25 A | $2.64 |
| 20 kW | 19.2 kW, about 65,500 Btu/h | Two circuits: 55/60 A and 50/50 A | $3.52 |
Cost per hour uses EIA's July 2026 US residential average of 18.31 cents per kWh; winter rates may differ.
- Voltage changes output. At 208 V the Trane "10 kW" kit gives 7.20 kW and needs a 48 A circuit on a 50 A breaker. Lennox's June 2025 R-32 submittal agrees: its 10 kW kit on a 3-ton MMD036S6 gives 9.18 kW at 230 V on a 60 A breaker.
- 15 and 20 kW kits need two circuits, which means panel space and amperage your service must have.
- The nameplate sets the circuit. Goodman's AMST manual: "fuses or circuit breakers are to be sized larger than the equipment MCA but not to exceed the MOP." New or resized circuits are licensed-electrician work; see our AC electrical scope guide.
Why a heat pump changes the math
Strips have a coefficient of performance (COP) of 1. A heat pump moves heat instead of making it: at COP 2 it delivers the 10 kW strip's 32,800 Btu/h for 4.8 kW, about $0.88 an hour, and at COP 3 for 3.2 kW, about $0.59. Real seasonal COP depends on the equipment and your winter, and the strips stay as backup. For heating comparisons, including gas, see heat-pumps.guide's heat pump vs gas furnace running cost by state and backup heat guide.
Can an air handler replace a furnace?
Yes. An air handler with strips is an electric furnace with a cooling coil built in. Before trading a gas furnace for one, check:
- Heating cost: $1.76 an hour for 9.6 kW of strips at 18.31 cents. A heat pump cuts that; see our central AC vs heat pump comparison.
- Electrical service: a 60 A breaker for a 10 kW kit and two breakers totaling 110 A for 20 kW, on Trane's data. Have an electrician confirm the panel and service.
- Airflow: Goodman's 3-ton AMST36CU1300 needs at least 1,170 cfm with kits up to 10 kW.
- Remaining gas appliances: a gas water heater or range keeps the gas line and its safety checks.
Condensate, placement and leak sensors
Water and refrigerant both meet the house at the indoor unit. Manuals and code set these rules:
| Situation | What is required | Source |
|---|---|---|
| Equipment above finished space | Secondary pan with float switch under the whole unit | Goodman AMST manual, May 2024 |
| Overflow could damage the house | Secondary pan, overflow line or shutoff switch | 2021 IRC M1411.3.1 |
| Cased coil where overflow could cause damage | Installer-supplied secondary pan with separate drain | Goodman and Daikin coil manual, Jul 2024 |
| Oil furnace below the coil | High-temperature drain pan, not the plastic one | Same coil manual |
| Horizontal or downflow Trane 5TEMCD04 | Airflow capped at 1,700 cfm to prevent water blowoff | Trane, Nov 2025 |
| Air handler in a humid, unconditioned space | 2-inch insulation wrap and a secondary pan recommended | Goodman AMST manual |
A2L leak sensors in new coils and air handlers
R-454B and R-32 are A2L, mildly flammable, so new indoor equipment carries refrigerant detection. Goodman's AMST manual warns: "A refrigerant leak detection system is installed. The unit must be powered on at all times except for service," and cites UL 60335-2-40, ASHRAE 15 and ASHRAE 15.2. On a leak, the system enters mitigation mode and runs the blower to dilute the refrigerant.
- Minimum area and airflow: 211 square feet of conditioned space and 380 cfm for Goodman's 3-ton AMST36CU1300; 185.87 square feet and 335.40 cfm for its 3-ton cased coil match.
- Furnace integration: the R-32 coil's sensor wires into a compatible Goodman, Amana or Daikin furnace board or an integration kit. With other brands, "if mitigation mode, or equivalent, is present but can't be disabled the furnace must be replaced."
- Zoning: the zone controller "must be powered through a zoning kit" so dampers open in mitigation mode.
- Duct accessories: possible ignition sources, such as electronic air filters, cannot sit in the ductwork.
Ask for the sensor test at startup; our quote comparison guide lists it with the other commissioning checks, and our condensate drain guide covers pans and float switches.
When to replace the furnace or air handler with the AC
A new R-454B or R-32 outdoor unit brings a new coil or air handler. The furnace is a separate call on age, condition and compatibility.
| Situation | Our call | Why |
|---|---|---|
| Furnace under about 10 years old, sound, compatible board | Keep it; replace the coil | Matched coil is already inside the AC band |
| Furnace older than 15 years | Price furnace and coil together, split out | ENERGY STAR's replace prompt; combined band runs $800 to $3,000 below two jobs |
| Furnace mitigation mode can't work with the new sensor | Replace the furnace | Goodman's coil manual requires it |
| Air handler with an R-410A coil, new A2L outdoor unit | Replace the air handler | The coil inside is part of the old refrigerant system |
| Young R-410A system, failed outdoor unit only | Repair or like-for-like R-410A | EPA allows repair components |
| Blower motor failed, rest of system young | Replace the motor | Fixr: $300 to $1,000 |
ENERGY STAR's replacement page flags furnaces "more than 15 years old" and air conditioners "more than 10 years old," though its central AC specification itself ended February 1, 2026. Our lifespan guide plans around 15 years for an AC, and Lennox says blower motors "typically last about 10-20 years" (April 4, 2025); see how long an air conditioner lasts and, for one failed part, the repair or replace guide. Do not replace a sound furnace because it suits the contractor: get the AC-only and furnace prices as separate lines.
Worked examples
These are labeled illustrations built from the bands and data above, not quotes.
Example 1. Gas-heated home, AC and coil replacement. A 3-ton R-410A air conditioner installed in 2012 has failed. The 80% gas furnace is 9 years old, passed its last safety inspection, and its maker offers a board or kit that accepts an A2L coil sensor.
| Line | Low | High |
|---|---|---|
| Standard-tier 3-ton AC with matched cased coil | $6,000 | $9,800 |
| Furnace kept | $0 | $0 |
| Total | $6,000 | $9,800 |
| Alternative: furnace and coil replaced too | $9,000 | $16,800 |
Verdict: keep the furnace, 6 years short of ENERGY STAR's 15-year prompt and compatible with the new sensor. Check the quote for an AHRI certificate that is coil-only (RCU-A-C) or names this furnace (RCU-A-CB), the coil model and refrigerant, the sensor wiring, and the blower tap set to the outdoor unit's specified airflow. At 17 years, the combined job would be worth pricing against $9,800 to $19,800 for two separate jobs.
Example 2. All-electric condo with an air handler and 10 kW strips. A 2-ton cooling-only system in a hallway closet, with a 10 kW heat kit, both from 2010. The condo has no gas.
| Line | Low | High |
|---|---|---|
| Standard-tier 2-ton AC base | $5,000 | $7,800 |
| New air handler instead of a coil | $1,500 | $3,500 |
| New circuit, only if the existing one does not fit | $0 | $1,800 |
| Total | $6,500 | $13,100 |
The circuit line is $0 if the existing heat-kit circuit fits the new nameplate, and our model's $400 to $1,800 if not. Trane's 2-ton 5TEMCB02AV21DA with a 10 kW kit needs a 54 A minimum circuit ampacity and a 60 A maximum breaker at 240 V; on 208 V the kit gives 7.20 kW, not 9.60 kW. The strips cost $1.76 an hour at 240 V, about $176 per 100 hours. The condo is far above the roughly 210 square feet Goodman lists as the minimum conditioned area for its 2- and 3-ton A2L air handlers, but the closet sits over a neighbor's ceiling, so the quote needs a secondary pan and float switch. If winter bills matter, price a heat pump with the same air handler first; heat-pumps.guide covers that comparison.
Quote red flags
- "Condenser replacement" with no indoor model number, or a new R-454B or R-32 outdoor unit on the existing R-410A coil.
- No AHRI Certified Reference Number, a certificate whose region excludes your state, or a blower-coil SEER2 that names a furnace you do not have.
- No plan for wiring the coil's leak sensor to your furnace, no zoning kit on a zoned system, or an electronic air cleaner left in the ducts without the manufacturer's approval.
- Heat strip size given only as "10 kW" with no breaker, wire size or voltage, or a breaker that exceeds the nameplate maximum.
- No static pressure or airflow reading planned at startup, with the blower left on its factory tap.
- An attic or above-ceiling unit with no secondary pan or float switch.
- A furnace replacement bundled into one lump total with no AC-only price.
If a quote has two or more of these, send it for an independent quote review before you sign.
FAQ
What is the difference between an air handler and a furnace?
Both hold the blower that moves air through your ducts. A furnace also burns gas, propane or oil, and needs a separate cased evaporator coil on top for air conditioning. An air handler holds the blower and coil in one cabinet and heats with electric strips, a heat pump, or both. AHRI rates an air handler as coil with blower (RCU-A-CB) and a furnace coil as coil only (RCU-A-C), unless the coil is certified with a specific furnace.
Do I need a furnace for central air?
No. Central air needs an indoor coil and a blower, and a furnace is just one way to provide the blower. Homes without gas use an air handler, and packaged units put the coil and blower outdoors. A split system cannot run on its outdoor unit alone.
Can an air handler replace a furnace?
Yes. An air handler with heat strips works like an electric furnace with a built-in cooling coil, and a 10 kW kit needs a 60 A breaker at 240 V on Trane's data. Strips cost about $1.76 an hour at the July 2026 US average electricity price, so if they would carry much of the winter, price a heat pump with the air handler too. Have an electrician confirm the panel capacity first.
What is an evaporator coil, and how long does it last?
It is the indoor heat exchanger where refrigerant evaporates, absorbing heat and pulling moisture out of the air. It sits on top of a furnace or inside an air handler, with a drain pan underneath. This Old House puts coil life at 10 to 15 years and a 3-ton replacement at $700 to $2,350 installed (April 2026).
Can I replace the outdoor AC unit and keep my old indoor coil?
Only when the manufacturer approves that exact pair and an AHRI certificate exists for it, which in practice means a like-for-like R-410A repair. A new R-454B or R-32 outdoor unit needs a coil approved for that refrigerant, with the matching metering device and a leak sensor. Manufacturer manuals state that unmatched systems are not permitted.
How much does it cost to run electric heat strips?
Multiply the strips' kilowatts by your electricity rate. At the July 2026 US residential average of 18.31 cents per kWh, a 5 kW kit costs about $0.88 an hour, a 10 kW kit $1.76 and a 20 kW kit $3.52. A heat pump at a COP of 2 to 3 delivers the same heat for one-half to one-third of that.
What we could not verify
- An installed price for heat strips. No primary, dated source prices it. Carrier's 2026 air handler guide calls a heat strip "an often-required add-on" without a price. Ask for it as a separate line.
- A national installed price. No federal agency publishes one. Component rows are cost guides citing their own data; AC totals are our model's planning bands, not measured averages.
- Air handler lifespan. We found coil and blower motor figures, but no primary source for the cabinet as a whole.
- Current PSC blower wattage. Furnace fans have had to meet DOE's FER limits since July 3, 2019, and we found no current PSC table, so we used DOE's coil-only default of 441 W per 1,000 scfm.
- Which furnaces accept another maker's A2L coil sensor. Goodman says to check each furnace manual. Get the answer for yours in writing.
- Winter electricity prices. Cost per hour uses EIA's July 2026 average; your utility's winter rate may differ.
- The text of UL 60335-2-40. It is not free to read, so the leak-detection rules here come from manufacturer manuals that cite it.
Sources
All sources checked October 16, 2026.
- eCFR: 10 CFR 430.32, energy conservation standards, including central air conditioners (c) and furnace fans (y)
- eCFR: 10 CFR 429.16, rating requirements for central air conditioners and heat pumps
- DOE: Test procedure for central air conditioners and heat pumps, final rule, 90 FR 1224 (January 7, 2025)
- DOE: Energy conservation standards for residential furnace fans, final rule, 79 FR 38130 (July 3, 2014)
- AHRI: AHRI type definitions
- AHRI Directory of Certified Product Performance
- MRCOOL: AHRI certificates for the HAC13036FA outdoor unit, December 12, 2024
- Goodman AMST R-32 air handler installation and operating instructions, IO-4011B, May 2024
- Goodman and Daikin upflow/downflow coil installation instructions, IO-4012C, July 2024
- Trane: 5TEMC variable speed air handler product data, AHR-PSD012B-EN, November 2025
- Lennox: V1EHK0 electric heat kit submittal for R-32 air handlers, June 2025
- EIA: Electric Power Monthly, Table 5.6.A, average price of electricity by state, July 2026, released September 24, 2026
- This Old House: Evaporator coil replacement cost, updated April 6, 2026
- Fixr: Heat pump repair cost, January 21, 2026
- Carrier: How much does an air handler cost, 2026 price guide
- Carrier: Gas furnace replacement guide, 2026
- Carrier: Downflow furnace guide
- EPA: Technology Transitions HFC restrictions by sector, updated August 28, 2026
- ENERGY STAR: When to replace heating and cooling equipment
- ENERGY STAR: Furnace and central air conditioner specification sunset
- Lennox: HVAC blower motor, April 4, 2025
- International Code Council: 2021 International Residential Code, Chapter 14, Section M1411
How this guide is checked
Written by Air Conditioner Guide Editorial Team. Editorial review by Air Conditioner Guide Editorial Team, last reviewed October 16, 2026. We check the sizing logic, quote-scope claims, and sources. No affiliate ranking bias.
Have a proposal?
Check the quote before you sign.
We'll look at the model match, capacity basis, install scope, warranty, and missing questions. Free, independent, no lead auction.
Check my quoteRelated guides

Central AC and Furnace vs Heat Pump: Which Replacement Wins?
Compare AC-plus-furnace and heat pump replacement costs, operating costs, ductwork, and climate fit, with EIA rates and a worked break-even example.
Read the guide
AC Condensate Drain Clogged? Fixes, Code and 2026 Costs
A clogged AC condensate drain costs $75 to $250 to clear. Signs, safe DIY steps, IRC float switch and trap rules, plus pump and water damage costs.
Read the guide
AC Line Set Reuse: 2026 Sizes, Costs and the A2L Rules
Can you reuse an AC line set? Sizes by tonnage from four manufacturers, R-454B, R-32 and R-22 reuse rules, the test steps and 2026 replacement costs.
Read the guide